Single component fire-retardant polyurethane foam PU
Single component fire-retardant polyurethane foam PU  - 1
Single component fire-retardant polyurethane foam PU  - 2

For detailed information, other images and documents, please select individual articles from the following table.

Single component fire-retardant polyurethane foam PU

Fireseal - passive fire protection systems
Fire resistant to EI 240

See product details

Available in 1 version

Individual price display after login

Exclusively for trade customers

Register now and access more than 150,000 products

Variants

Exclusively for trade customers

Register now and access more than 150,000 products

Call customer service: +41 61 705 91 00

Prices for customers after login

  • Can be cut, ground, sanded, painted, perforated and plastered once cured

  • High adhesive strength

  • Good resistance to water, chemicals, cleaning agents and microorganisms

  • Very low emission of volatile organic substances (EC 1 Plus)

  • High resistance to fire for up to 240 minutes (depending on the type of application)

  • Can be used for any length of joint, both with and without rock wool

  • High fire resistance times even in walls only 100 mm thick

  • Thanks to its consistency (foam), it adapts to geometries and can be used for joints of various sizes

  • Quick application and high yield (1 cylinder = approx. 40 l)

  • Easy to extrude using a conventional PU foam gun
Notice

Because the material is not intumescent, it is not suitable for the fire-retardant sealing of joints containing pass-through elements (pipes, cables etc.). Use other Fireseal systems


Do not use for sealing flues



Certificates: www.wuerth.it/progettisti



Observe the positioning specifications in each case

Fire resistance values in accordance with EN13501-2 - wall application
Min. wall thickness/mmJoint directionSample nameJoint width/mmThickness of rock wool mm (density ≥ 40 kg/m3)PU foam thickness/mmFire resistance
100VerticalA106020*EI 180
B20-100EI 60
HorizontalF10-100EI 120
G206020*EI 120
150VerticalC30-150EI 60
D4010025*EI 120
E50-150EI 30
HorizontalH3010025*EI 240
I40-150EI 60
L5010025*EI 180
*Application on both sides of the wall
Fire resistance values in accordance with EN13501-2 - ceiling application
Min. ceiling thickness/mmSample nameJoint width mmThickness of rock wool mm (density ≥ 40 kg/m3)PU foam thickness/mmFire resistance
150A1010025*EI 120
B20-150EI 120
C30-150EI 120
D4010025*EI 240
E50-150EI 60
F60-150EI 45
G7010025*EI 120
*Application on both sides of the ceiling
Application area
Instructions